SYN-6.2 Synchronizer
The device provides tracking of a generator's voltage and frequency to the mains, in order to switch it on in addition to the network at minimum difference and the same phase angle.
This unit measures voltage and frequency of two AC power networks between 2 phases each. As soon as control over the control input has been released, the SYN-6 generates corresponding offset pulses for the generator voltage and frequency. If both values differ within the preset tolerances to the leading mains, the unit emits a synchronisation pulse. In order to compensate delays of the switching elements, the sync impulse is given prematurely by the lead time, prior to the calculated sync time.
The voltages and frequencies are displayed during operation. In addition, LEDs indicate all input and output switching states. This also applies when monitoring the voltage and frequency deviations permissible for synchronisation. All tolerances and nominal values are adjustable via parameters.
Back to overview
Technical data |
|
|---|---|
| Auxiliary Voltage | 24 V DC optional: 12 V DC, 100V AC or 230V AC |
| Power consumption | 4 W at 24 V DC, approx. 5 VA at 230 V AC |
| Measurement voltage | min. 70 V AC |
| Frequency | 45 ... 65 Hz |
| Leading time | 10 ... 500 ms |
| Frequency differential | max. 0.01 ... 0.99 Hz, min. 0.05 ... 0.50 Hz Voltage differential 1 ... 15 % |
| Digital inputs | 12 V, 8 mA |
| Relay outputs | 2 A / 230 V AC |
| Protective class | IP20 |
| Ambient temperature | -20 ... +55 ºC |
| Dimensions | W / H / D : 100 x 75 x 110 mm Accessories: switching panel installation frame |
| Download PDF | |
| Ordering information | SYN-6.2 / 12V DC Version: E1835 SYN-6.2 / 24V DC Version: E1846 SYN-6.2 / 100V AC Version: E1347 SYN-6.2 / 230V AC Version: E1847 |