SYN-7 Synchroniser Relay
The synchroniser relay SYN-7 adjusts voltage and frequency of a generator to the mains, in order to connect it at a minimum difference of frequency and voltage, and at the same phase position. Depending on its configuration, the SYN-7 is monitoring sense of rotation, voltage difference and asymmetry.
Voltage measurement is done as 2-, 3- or 4- wire measurement, according to the preset parameterisation. The frequency measurement generally is on L1 and L2. In island mode, the desired frequency and voltage are internally set by the device. A separate variant of the SYN-7 is available for measuring voltages <= 100 V.
Back to overview
Technical data |
|
|---|---|
| Auxiliary Voltage | 24V DC (18 ... 36 V) optionally 230V AC / 12 V DC |
| Power consumption | approx. 4 W at 24 V DC, approx. 6 VA at 230 V AC |
| Digital inputs | LowActive (Contact Voltage 12 V, 5 mA, opto-decoupled), accord. to DIN |
| Relay Outputs | 230 V / 50 Hz / 2 A (potential-free) |
| Analogue Outputs | 0/2 ... 10 V +/- 0.05 V max. 10,5 V |
| Measuring Range | approx. 50 up to 230 / 400 V, tolerance < 0,5 % of full scale (270 / 480 V) |
| Frequency Measurement | 35.0 Hz up to 65.0 Hz about approx. 50 V L-N +/- 0.05 Hz |
| Leading time | adjustable 50 ... 500 ms |
| Adjustment Pulses | adjustable 0.1 s up to 100 s |
| Max. Frequency Difference | adjustable 0.1 ... 1.0 Hz |
| Max. Voltage Difference | adjustable 1 ... 15 % |
| Climatic Conditions | acc. to DIN EN 60204-1 ( 05-2010 ) |
| Ambient temperature | operation: -20 ... +55 °C transport/storage: -25 ... +55 °C |
| Dimensions | W / H / D 100 x 75 x 110 mm DIN top-hat rail mounting 35 mm |
| Download PDF | |
| Software | |
| Ordering information | SYN-7 / 230V AC: E1358 SYN-7 / 24V DC: E1359 SYN-7 / 100V / 230V AC: E1657 SYN-7 / 100V / 24V DC: E1658 |